Low Voltage Disconnects - LVD1U Series
ONE MOUNTING POSITION HIGH LOW VOLTAGE DISCONNECT PANELS |
|
|||||||||||||
Unipower Telecom’s LVD1U Series of low-voltage disconnect panels are designed for maximum flexibility. They can be connected for either load or battery disconnect. The one mounting position (1.75 inches) high panels can also be configured as single or dual (A/B) disconnects.
The disconnect contactor is rated at 70 amperes. A 100-ampere max. battery circuit breaker is also incorporated into each unit.
Optional is a bypass switch which allows the user to bypass the LVD contactor. An LVD or battery alarm is indicated by a red LED. Form C relay contacts also indicate an LVD or battery breaker alarm.
The A and B sections of the dual LVD panel can be separately configured for 24 or 48 volts and positive or negative ground. The panels come with brackets that permit mounting in either a 19- or 23-inch relay rack. They can be mounted from the front of the rack with offsets every quarter-inch from front to back to align with existing rack-mounted equipment. |
||||||||||||||
NOTE: To print out the Low Voltage Disconnects data sheet, you may print from your browser or see a detailed .pdf spec sheet from within Adobe Acrobat. If you need Adobe Acrobat Click Here to download the plug-in. |
||||||||||||||